RoofCalc.

Roof ventilation calculator

The net free area your attic needs, split into intake and exhaust, then converted into the ridge vent length and the number of vents you can actually buy.

Default scenario: 1,500 sq ft attic at 1/150, ridge vent at 12.5 sq in per foot, 50 sq in vents. Change a field and recalculate for your roof.

Your result

1,440 sq in of net free area

at 1/150, split into 720 sq in intake and 720 sq in exhaust

Attic floor area 1,500 sq ft The vented space, not the roof surface
Total net free area 1,440 sq in 1,500 × 144 ÷ 150
Intake at the eaves 720 sq in 50% of the total (IRC R806.2)
Exhaust at the ridge 720 sq in 50% of the total
Ridge vent at 12.5 sq in/ft 58 lf 720 ÷ 12.5, rounded up
Individual vents 15 vents At 50 sq in each
  • Net free area is the open area after the screen, baffle and louvers are subtracted, not the size of the hole in the roof.
  • The 50/50 split matters more than the total: exhaust without intake pulls conditioned air out of the house instead of cooling the deck.

Before you buy

  • Only use 1/300 when a vapor retarder is on the warm side and intake and exhaust are balanced (IRC R806.2 exception).
  • Do not mix a ridge vent with other exhaust vents at the same height; the stronger one short-circuits the other.
  • Check that soffit vents are not blocked by insulation. Baffles keep a 1 in channel open at the eaves.

Other options

  • 1/300 with a vapor retarder — Halves the requirement to 720 sq in, but only where the code exception applies.

The one number the code cares about

Attic ventilation is sized by net free area, not by the size of the vent. The International Residential Code requires at least 1 sq ft of net free area for every 150 sq ft of vented floor area, and at least half of it at the upper portion of the space. For a 1,500 sq ft attic that is 10 sq ft, or 1,440 sq in, split 720 sq in low and 720 sq in high.

The ratio is based on the floor of the attic, not the sloped roof area. A 1,500 sq ft ceiling under a 10:12 roof has far more roof surface than 1,500 sq ft, but the ventilation requirement does not change. Using the roof area instead of the floor area is the most common way to over-order vents.

Intake matters as much as exhaust

A ridge vent without soffit intake does very little. The ridge can only expel air that comes in somewhere, and if the eaves are blocked by insulation or have no vents, the ridge pulls air down through the house instead. That cools the attic slightly and costs you heating and cooling energy all year.

The code's 50% split is the design target: half the net free area at the eaves, half at the ridge. Real installations often come up short on intake because the soffit is narrow or the insulation has been pushed to the edge. Baffles keep a 1 in channel open between the insulation and the roof deck, and they are cheap compared with adding vents later.

Net free area, not vent size

Every vent is labelled with its net free area. A soffit vent with an 8 × 16 in face does not provide 128 sq in; the louvers and screen reduce it, usually to around 50 sq in. A ridge vent is rated in square inches per linear foot: GAF Cobra RidgeRunner is 12.5 and GAF Cobra Rigid Vent 3 is 18, so even one maker's line varies by almost half.

That range is why the calculator lets you type the product's rating. Using 18 sq in per foot when you bought a 12.5 sq in product undersizes the vent by about a third, and the attic tells you about it in August.

The 1/300 exception, precisely

The code allows half the vent area, 1/300, only when two conditions are met: a Class I or II vapor retarder is installed on the warm side in climate zones 6 to 8, and between 40 and 50 percent of the required area is at the upper vents. It is not a general "balanced ventilation" discount.

GAF recommends 1 sq ft per 300 sq ft as a minimum for its ridge vents, which is a manufacturer's minimum and not a substitute for the code path. If you cannot document the vapor retarder and the climate zone, use 1/150. The difference on a 1,500 sq ft attic is 720 sq in, which is a lot of vent to add later.

What a balanced system looks like

Ridge length is often the limit

A 40 ft house with a simple gable has about 40 ft of ridge. At 12.5 sq in per foot that is 500 sq in of exhaust, against the 720 sq in a 1,500 sq ft attic needs. The ridge alone is short by 220 sq in, so the plan needs either a second exhaust path or a smaller attic. This is normal on older houses, and it is why the calculator reports both the ridge length and an individual vent count.

On a hip roof the ridge is shorter still, and the hips cannot take a ridge vent. Static vents near the ridge, or a balanced set of gable vents, fill the gap.

Vented, unvented and cathedral ceilings

An unvented attic is a legitimate design: the insulation is on the underside of the roof deck, the attic is inside the conditioned envelope, and there is no vent area to calculate. It needs an air-impermeable insulation and a building official who accepts the assembly. A cathedral ceiling with insulation in the rafter bays is harder to ventilate because there is no open attic; it needs a 1 in vent channel above the insulation from eave to ridge, which is a different calculation from this one.

This calculator assumes a conventional vented attic with a flat ceiling. If your attic is conditioned or your ceiling is cathedral, the number here does not apply.

What ventilation does not fix

A worked example

A 1,500 sq ft attic at 1/150 needs 1,500 × 144 ÷ 150 = 1,440 sq in. Half is 720 sq in of intake and 720 sq in of exhaust. With a ridge vent rated at 12.5 sq in per foot, the exhaust needs 720 ÷ 12.5 = 57.6 ft, so 58 ft of ridge. With 50 sq in soffit vents, the intake needs 720 ÷ 50 = 14.4, so 15 vents.

Frequently asked

How much attic ventilation does a 1,500 sq ft attic need?

At the 1/150 rule, 1,440 sq in of net free area: 720 sq in of intake at the eaves and 720 sq in of exhaust at the ridge. That is 10 sq ft of open area in total.

When can I use 1/300 instead of 1/150?

Only where the code exception applies: a Class I or II vapor retarder in climate zones 6 to 8, with 40 to 50 percent of the vent area at the upper vents. Elsewhere the baseline is 1/150.

How many feet of ridge vent do I need?

Divide the exhaust net free area by the product’s rating. At 12.5 sq in per foot, 720 sq in needs 58 linear feet of ridge vent, which is more than most houses have; add gable or static vents if the ridge is short.

What is net free area?

The open area left after the screen, louvers and baffle are subtracted. A vent with a 50 sq in opening might have 25 sq in of net free area. Use the number on the label, never the hole size.

Can I mix a ridge vent with a powered fan?

Usually no. A powered exhaust at the ridge or a gable fan can short-circuit a ridge vent and pull air from the nearest opening instead of the eaves, so the attic stays hot and the fan runs constantly.

Where these numbers come from

Figures that come from our own arithmetic rather than a published table are marked house rule on the method page. No price is shown anywhere on this site because no supplier publishes one national figure that would be true for your town and your roof.